Zur Startseite gehen
Ihr Konto
Anmelden
oder registrieren
Übersicht Persönliches Profil Adressen Zahlungsarten Bestellungen
0,00 €*
Home
SSA, SSB, SSBC, SSC, SSFP, SSKM, SSLT, SSMT, SST
00T, 3T
A, LO, MO, OP
BL
LBI Sicherungshalter
Bottle D & DO
JF, JHU, JPU, JSU
SS, NS, MES
LA, LC, LD, LK
LCF Sicherungshalter
LPV Zylindrische Sicherungen
CTC, CTCP
FBLBI Sicherungshalterleisten
ME, MF
TB, TBC, TCP, TFP, TIA, TIS, TLM, TTM
LST
Halbleiterschutzsicherungen
MD
KCC, KDC, PCC, PDC, TCC, TDC
Modular-Sicherungshalter
NH 500V
PL
LPC Pullcap Sicherungshalter
LGP Reyrolle Pattern
SL Neutralleiter
Slydlok Sicherungshalter und Sicherungen
Zeige alle Kategorien RedSpot Fuse Holders Maintenance Zurück
  • RedSpot Fuse Holders Maintenance anzeigen
  • SSA, SSB, SSBC, SSC, SSFP, SSKM, SSLT, SSMT, SST
  • 00T, 3T
  • A, LO, MO, OP
  • BL
  • LBI Sicherungshalter
  • Bottle D & DO
  • JF, JHU, JPU, JSU
  • SS, NS, MES
  • LA, LC, LD, LK
  • LCF Sicherungshalter
  • LPV Zylindrische Sicherungen
  • CTC, CTCP
  • FBLBI Sicherungshalterleisten
  • ME, MF
  • TB, TBC, TCP, TFP, TIA, TIS, TLM, TTM
  • LST
  • Halbleiterschutzsicherungen
  • MD
  • KCC, KDC, PCC, PDC, TCC, TDC
  • Modular-Sicherungshalter
  • NH 500V
  • PL
  • LPC Pullcap Sicherungshalter
  • LGP Reyrolle Pattern
  • SL Neutralleiter
  • Slydlok Sicherungshalter und Sicherungen
  1. Footer Bussmann
  2. RedSpot Fuse Holders Maintenance

Method of cabling

Front connected fuse holders

  • Remove Red nylon insulating shroud to release cable sleeve.
  • Remove cable sleeve.
  • Fit cable sleeve over cable.
  • Fit conductor into fuse base terminal and tighten cable clamping screw to secure.
  • Replace Red nylon shroud taking care it holds the cable sleeve in position by locating the shroud in the groove provided by the sleeves.

Cable selection and termination

  • Ensure cable sizes are correctly chosen in line with the IEE Wiring Regulations (BS 7671), making due allowance for:
i. Grouping of cables (correction factor Cg).
ii. Ambient temperature / internal enclosure temperature (correction factor Ca).
  • Ensure that maximum cable core temperature is restricted to 70°C or less.
  • Ensure adequate cable length is provided for interconnections between fuse holders or other components. This will prevent possible heat input to the fuse holder which could result in overheating.
  • If using multi-stranded cables / Tri-rated cables the bared strands should be crimped in thin wall copper ferrules in order to consolidate the strands. The following points should be taken into account:
i. The inside diameter of the ferrules should match that of bared cable ends.
ii. The ferrule lengths should be the same length as the cable entry tunnel in the fuse base terminals.
iii. The termination screw should compress the wall of the ferrules, providing further consolidation of the cable strands within the ferrule.
  • When used in banks, ensure that the diversity factors recommended in BS5486 Part 11, Factory Built Assemblies, are applied. If the number of fuse holders banked together exceeds 12 a 0.6 diversity factor may be used.
  • For applications when there is insufficient or no diversity applied, adequate compensation should be made by a combination of some, or all, of the following:

i. Utilise higher standard current rated fuse links, or motor rated fuse links.
ii. Increase the cable size.
iii. Ensure that fuse holders in the bank are separated by at least 5mm.
iv. Ensure that there is adequate spacing between fuse banks if they are stacked vertically. Typically, depending on rating, this would be 30-50mm.
v. Incorporate natural or forced ventilation.

These measures should ensure that the heat is adequately exported
from the fuses.

  • Sharp bends in cables, especially near termination points, should be avoided in order to prevent damage to cable cores or insulation and to ensure that no mechanical strain, is put on the contact block in the fuse
    base.
  • The minimum torque values detailed in the attached table should be applied to cable terminal and fuse link fixing screws.

 

 

Important note:
These products should be installed, commissioned and maintained by, or under the supervision of, a competent person, in accordance with current Electricity at Work Regulations, IEE Regulations for the Electrical Equipment of buildings, Statutory requirements and any other specific instructions issued by GE Power Controls Ltd. These notes assume throughout that the product is isolated from the supply during installation or maintenance. It is essential that this is done before commencement of any work. Any covers, or other safety measures which are removed during installation or maintenance must be replaced on completion.

(Information from Red Spot catalogue.)

Service-Hotline

Unterstützung und Beratung über unser: sales888@casadaa.com +49 202 702031 Montag-Freitag 10:00 - 16:00 Uhr ME(S)Z.

Oder über unser Kontaktformular.
Service
  • Über Uns
  • Impressum
  • Datenschutz
  • AGB für Privatpersonen
  • AGB für Geschäftskunden
  • Exportkunden
Links
  • Firmen Webseite
  • LinkedIn
  • Facebook
  • Instagram
  • Youtube
Casadaa Distribution Shops für Geschäftskunden
  • Eaton Bussmann Sicherungen Shop: BussmannSicherungen.de
  • Lawson Fuses Ltd. Shop: BS88.eu
  • Relais Shop: RelayGo.es
  • Eaton Moeller series Shop: LWD24.com
  • Waermewandler.info
Casadaaa Service für Geschäftskunden
  • Casadaa Personalvermittlung
Footer Bussmann
  • Bussmann Sicherungen von Casadaa
  • RedSpot Fuse Holders Maintenance
  • RedSpot Fuse Link Selection

    * Alle Preise exkl. gesetzl. Mehrwertsteuer zzgl. Versandkosten und ggf. Nachnahmegebühren, wenn nicht anders angegeben.

    Diese Website verwendet Cookies, um eine bestmögliche Erfahrung bieten zu können. Mehr Informationen ...